PL EN

Dimensions:

reqv-wymiary_1
reqv-wymiary_2
reqv-wymiary_3

Technical data

Models reQ V.400 HRV / ERV reQ V.550 HRV / ERV
Maximum air expenditure 400 m³/h* with 150 Pa (HRV)
with 180 Pa (ERV)
550 m³/h* with 150 Pa (HRV)
with 180 Pa (ERV)
Efficiency of heat recovery up to 95% (HRV) / up to85% (ERV)**
Exchanger type
counterflow
Kind of exchanger HRV: with heat recovery
ERV: with heat and moisture recovery (entalpical)
Exchanger material HRV: synthetic material
ERV: synthetic material + polymer membrane
Moisture recovery efficiency
without (HRV) / up to 65% (ERV)
Energy consumption
100 m3/h (50 Pa) 25 W (HRV)
24 W (ERV)
200 m3/h (50 Pa) 43 W (HRV)
42 W (ERV)
250 m3/h (100 Pa) 74 W (HRV)
72 W (ERV)
400 m3/h (100 Pa) 157 W (HRV)
154 W (ERV)
400 m3/h (150 Pa) 187 W (HRV)
184 W (ERV)
550 m3/h (150 Pa) 272 W (HRV)
267 W (ERV)
The level of sound power emitted by the housing at a distance of 1 meter 100 m3/h (50 Pa) 24 db(A) 200 m3/h (50 Pa) 30 db(A)
250 m3/h (100 Pa) 33 db(A) 400 m3/h (100 Pa) 42 db(A)
400 m3/h (150 Pa) 43 db(A) 550 m3/h (150 Pa) 48 db(A)
Sound power level – nominal value 35 db(A) 41 db(A)
Wentilators Radial with DC EC motors ( ebm-papst)
Energy efficiency class A***
Bypass Automatic, 100% bypass of suply air
Communication Built-in Wi-Fi module control via mobile application ) iOS 12.0 and Android 6.0 or later ) and  WWW browser
Smart home system YES (REST API) – additional information HERE
Diameter of the connection stubs Isolated (EPP) 4 x Ø200 mm
Filters Pleated class M5**** / ePM10 75%***** (optional airflow: anti-smog F9**** / ePM1 80%*****)
Preheater Built-in, easly controlled PTC, maximum power 1.5 kW
Airflow constant system YES
Humidity sensor YES, built-in
CO2 sensor YES, built-in
Case material Stainless stell
Condensation drainage YES (the set includes a dry siphon – Ø32/Ø40 mm)
Dimensions ( height x width x depth)  981 x 1041 x 442 mm
Mounting

Stainless stell mounting console for wall-mounting.

Siphon

Optional anti-smog filter F9

* with M5 class filter

** The recuperator reQnet reQ V. in the ERV version,  due to the enthalpy exchanger, does not meet the requirements of the “Clean Air 2019” program for applications submitted before 15.05.2020. The statement to the “Clean Air 2020” program for applications submitted after 15.05.2020 can be found on the pricelist24.pl website in the product tab.

*** for temperate climate in accordance with Directive 2009/125/EC and Commission Regulation 1254/2014

**** Acording to EN779

***** Acording to ISO 16890

przepywy_reQ-V_oslabione
czerpnia_ico

INTAKE: fresh air taken from outside via a duct marked as INTAKE goes to the heat exchanger

czerpnia_ico

SUPPLY: the fresh air heated in the exchanger from the outside by the SUPPLY is brought into the rooms

czerpnia_ico

EXHAUST: the used air is taken out of the rooms, in the kitchen, toilet or bathroom through the EXHAUST

czerpnia_ico

OUTLET: the air cooled in the exchanger is discharged to the outside

Flow characteristics:

charakterystyka_przeplyw_1
charakterystyka_przeplyw_2

Mounting system:

On the floor vertically

System montażu: Na podłodze w pionie
System montażu: Na podłodze w pionie

On the wall

System Montazu3
System Montazu4

Console

In the case of mounting on the wall, you need to mount the recuperator using the special console included in the set.

The console is mounted to the wall using dowels. For this, you need to make 6 holes – as in the drawing.

The choice of pins and mounting screws depends on the material from which the wall was made.

Two ways of communication